Prices  p/n: B78120014, Type: CTUB101-CTBC60  Bender  Germany

BRAND Bender
Product p/n: B78120014, Type: CTUB101-CTBC60
Description current transformer
Internal code IMP4123451
Weight 0.53
Custom code 90303370
Technical specification LV current transformer Primary current 250 A Line feed-through diameter:60 mm Rated voltage: 800 V Over voltage category III Operating height: ≤ 2000 m above sea level Rated surge voltage: IC1/IC2 8 kV Rated insulation voltage (reinforced insulation): IC1/IC2 800 V. Pollution level: 2 Supply voltage US: DC ±12 V. Us Workspace: ±2% Ripple US: ≤ 1% Own consumption: ≤ 2.5 W Inrush current 500 mA (referred to the RCMA423) CTBC60 at IΔn = 30 mA: 160 A. CTBC60 at IΔn = 300 mA: 250 A. Measuring accuracy ± 1 % Test development: Yes Thermal rated continuous differential current Icth: 30 A. Thermal rated short-time current Ith: 2.4 kA/1 s. Rated surge current Idyn: 6 kA/40 ms Output Name: S1 (k), S2 (l) Scaling 400 mV/1 A. Max. voltage 10 V Max. Connection length 10 m Output resistance 172 Ω Protection class, installation (DIN EN 60529): IP40 Protection class, terminals (DIN EN 60529): IP20 Flammability class UL94 V-0